Product Detail

Cummins 50kW Silent Diesel Generator
Compact 50kW (63kVA) Cummins soundproof diesel generator set, designed for small offices, clinics, retail stores and light commercial standby power where quiet operation and reliability matter.
Key Specifications
| Prime power | 45 kW / 56 kVA |
| Standby power | 50 kW / 63 kVA |
| Engine | Cummins 4BT3.9-G2 |
| Alternator | Stamford / Leroy-Somer brushless |
| Voltage | 400/230V, 50Hz, 3-phase |
| Control | Deepsea or ComAp AMF controller |
| Noise level | ≤68 dB(A) @ 7m |
| Fuel tank | 120L built-in |
| Dimensions | 2100 x 950 x 1300 mm |
| Weight | 950 kg |
Features
- Cummins 4-cylinder diesel engine with proven global service network
- Acoustic canopy reducing noise to below 68 dB(A) at 7 meters
- Automatic voltage regulation (AVR) with digital control panel
- Integrated baseframe fuel tank for 8+ hours continuous running
- Automatic mains failure (AMF) start-up within 10 seconds
- CE, ISO9001 and emission-compliant package
Application Scope
- Small offices & clinics
- Retail stores & shops
- Light commercial standby
Problems It Solves
- Quiet backup power near offices and residences
- Reliable start-up when the grid fails
- Compact size for tight plant rooms
Manufacturing & Quality Testing
Every Kaichen diesel generator set passes through the same production line and test routine before it leaves our factory in Jiangsu. The process is built around one goal: the set arrives at your site ready to carry load on the first real outage, not after a month of debugging.
How each set is built
- Engine and alternator matching. We match the engine rating to the alternator at the exact power factor your site needs, not just at the nameplate number.
- Baseframe and tank. The skid is welded from steel plate, fitted with an integrated fuel tank, vibration isolators, and forklift slots before the engine is mounted.
- Wiring and control panel. Power and control wiring are routed in separate channels, terminal blocks are numbered, and the digital controller is pre-programmed for your voltage, frequency and ATS logic.
- Canopy or container. Silent sets are dressed with acoustic foam, vented panels and access doors; containerized sets receive weather-sealed doors, internal lighting and a socket for external power.
Load test before shipment
No set ships on a visual check. Each unit runs on our electronic load bank for a structured sequence, and the test report travels with the set:
| No-load run | Warm-up, oil pressure and charging voltage check |
| 25% load, 30 min | Stability of voltage and frequency, exhaust temperature |
| 50% load, 30 min | Governor response, fuel consumption, noise level |
| 75% load, 60 min | Cooling system, coolant temperature, belt tension |
| 100% load, 60 min | Full rated output, voltage regulation within ±1.5% |
| Overload 110%, 1 min | Protective shutdown and alarm verification |
Final inspection
- Insulation resistance and earth continuity tested after a damp-heat soak.
- All protective functions verified: over-speed, high water temperature, low oil pressure, over-current, emergency stop.
- Automatic transfer switch sequence tested end-to-end on a bench.
- Paint touch-up, cleaning, and a full spare-parts list packed in the toolbox.
CE and ISO 9001 certificates accompany each shipment. If you need a witness test, a third-party inspection (BV, SGS, TUV) report, or a site-specific FAT protocol, tell us before the set enters production and we will prepare it accordingly.